1105
2
Gateway for BL67 I/O system
Interface for DeviceNet™
BL67-GW-DN
●
3 decimally coded rotary switches
●
Degree of protection IP67
●
LEDs for display of supply voltage,
common alarm and bus errors
●
Interface between the BL67 system
and DeviceNet™
●
120/250/500 kbps
●
Two 5-pole 7/8" connectors for
fieldbus connection
Fieldbus
Fieldbus
Function principle
BL67 gateways are the head component of
a BL67 station. They are designed to inter-
face the modular fieldbus nodes to the hig-
her level fieldbus (PROFIBUS-DP,
DeviceNet™, CANopen, Ethernet).
All BL67 electronic modules communicate
via the internal module bus, whose data are
transferred to the fieldbus via the gateway,
so that all I/O modules can be configured
independently of the bus system.
3
4
5
2
1
1 = Shield
2 = V +
3 = V
4 = CAN_H
5 = CAN_L
3
4
5
2
1
1 = Shield
2 = V +
3 = V
4 = CAN_H
5 = CAN_L
Type BL67-GW-DN
Ident-No. 6827183
Supply voltage 24 VDC
Permissible range 11...26 VDC
Nominal current from module bus 600 mA
Max. field current supply 8 A
Max. system current supply 1.5 A
Transmission rate fieldbus 125/250/500 kbps,
2 decimally coded rotary switches
Fieldbus addressing range 0...63
Fieldbus adressing 2 decimally coded rotary switches
Service interface PS/2 socket for I/O-ASSISTANT
Fieldbus connection technology 2 x 7/8'', 5-pole
Power connection technology via DeviceNet™ cable
Fieldbus termination external
Operating temperature 0 ... +55 °C
Storage temperature -25 ... +85 °C
Relative humidity 5 to 95 % (indoor), Level RH-2,
without condensation (storage at 45 °C)
Vibration test according to EN 61131
Shock test according to IEC 68-2-27
Topple and fall according to IEC 68-2-31
and free fall according to IEC 68-2-32
Electromagnetic compatibility according to EN 61131-2
Degree of protection IP67
General technical data see page 21