Gateway for BL67 I/O system
Interface for CANopen
BL67-GW-CO
●
3 decimally coded rotary switches
●
Degree of protection IP67
●
LEDs for display of supply voltage,
common alarm and bus errors
●
Interface between the BL67 system
and CANopen
●
1 Mbps
●
Two 5-pole M12 connectors for
fieldbus connection
●
One 5-pole 7/8" connector for po-
wer connection
Fieldbus
Fieldbus
Power supply
Function principle
BL67 gateways are the head component of
a BL67 station. They are designed to inter-
face the modular fieldbus nodes to the hig-
her level fieldbus (PROFIBUS-DP,
DeviceNet™, CANopen, Ethernet).
All BL67 electronic modules communicate
via the internal module bus, whose data are
transferred to the fieldbus via the gateway,
so that all I/O modules can be configured
independently of the bus system.
2
3
45
1
1 = Shield
2 = V +
3 = V
4 = CAN_H
5 = CAN_L
4
13
2
5
1 = Shield
2 = V +
3 = V
4 = CAN_H
5 = CAN_L
3
4
5
2
1
1 = GND
2 = GND
3 = PE
4 = V
i
5 = V
o
Type BL67-GW-CO
Ident-No. 6827200
Supply voltage 24 VDC
Permissible range 18...30 VDC
Nominal current from module bus 600 mA
Max. field current supply 10 A
Max. system current supply 1.5 A
Transmission rate fieldbus 20 to 1000 kbps, DIP switch
Fieldbus addressing range 1...99
Fieldbus adressing 2 decimally coded rotary switches
Service interface PS/2 socket for I/O-ASSISTANT
Fieldbus connection technology 2 x M12, 5-pole
Power connection technology 5-pole male 7/8'' connector
Fieldbus termination external
Operating temperature 0...+55 °C
Storage temperature -25...+85 °C
Relative humidity 5 to 95 % (indoor), Level RH-2,
without condensation (storage at 45 °C)
Vibration test according to EN 61131
Shock test according to IEC 68-2-27
Topple and fall according to IEC 68-2-31
and free fall according to IEC 68-2-32
Electromagnetic compatibility according to EN 61131-2
Degree of protection IP67
General technical data see page 21
LED
77,5
145
32
13