EasyManua.ls Logo

Tyco 801AP - Main Menu Display

Tyco 801AP
10 pages
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
801AP
17A-05-AP
2 11/02
PAGE 10 of 10
MAIN MENU DISPLAY ACTIONS
‘Address Program’ Read/Writes the address of the connected addressable device
‘Analogue Values’ Displays the analogue values of the addressable device
‘Measure Temp.’ Measures temperature in degrees C and F (only available on detectors which have a
temperature sensing element)
‘Measure CO Level’ For CO detectors only. Gives values for CO levels in the measuring environment.
Normal value is zero PPM (parts-per-million)
‘Self Test’ Performs a self test if the detector has such a facility
‘Dirtiness’
Indicates the contamination level of the optical chamber expressed as a percentage,
where 100% is the fault level
‘Serial Number Displays the unique serial number of the addressable device
‘Manufacture Date’ Displays the date of manufacture of the device
‘Commission Date’ Displays the date of device commissioning
‘Device Type ID’ Displays the device type identification value
‘LED Mode’
Blnk - flashes each time the device is polled
Off - switches OFF the blinking option
Tst - tests of the LED
Digital Inputs Displays the status of the digital inputs in addressable devices
Digital Outputs Allows the user to set the digital output of the addressable device
Test RI Terminal Tests the Remote Indicator output
Test L2 Terminal Tests the Functional Base interface output
Backlight Switches the backlight ON/OFF
Auto-Power Off
Dn - decreases the time
Set - sets auto power OFF to the selected time
Up - increases the time
Store Settings This customises the Store Settings which are: Auto Power-off time and Customer Code.
Def - returns to default settings
ClU - clears ‘used addresses’ memory
Sto - stores changed settings
Customer Code Not normally used, but it should be set to the same as the customer code in the detector
Low Battery Indicates Low Battery by using a flashing cursor in the bottom right of the LCD display
CPU Reset Switch is accessed through a small hole at the rear of the unit near the label
Table 1: Functional Reference table
JM/jm 19
th
November 2002

Related product manuals