Internet Alarm Communicator Installation Manual
[035] Panel Firmware Update Begin
Default (FF) Program 00 disable or FF enable.
|____|____|
[036] Panel Firmware Update
Successful
Default (FF) Program 00 disable or FF enable.
|____|____|
[037] System Firmware Update Fail
Default (FF) Program 00 disable or FF enable.
|____|____|
[095] SA Incoming Local Port
Default (0000) Valid range: 0000 - FFFF.
|____|____|____|____|
[096] SA Outgoing Local Port
Default (0000) Valid range: 0000 - FFFF.
|____|____|____|____|
[097] SA Call Up IP
Default (000.000.000.000)
|____|____|____|____|
[098] SA Call Up Port
Default (0000) Valid range: 0000 - FFFF.
|____|____|____|____|
[099] SA Access Code
Default (FFFFFFFF) Valid range: 00000000 - FFFFFFFF.
|____|____|____|____|____|____|____|____|
Ethernet Receiver 1 Options
[101] Ethernet Receiver 1 Account Code
Default (0000000000)
Valid range: 0000000001 - FFFFFFFFFE.
|____|____|____|____|____|____|____|____|____|____|
[102] Ethernet Receiver 1 DNIS
Default (000000) Valid range: 000000 - FFFFFF.
|____|____|____|____|____|____|
[103] Ethernet Receiver 1 Address
Default (127.000.000.001)
|____|____|____||____|____|____||____|____|____||____|____|____|
[104] Ethernet Receiver 1 UDP Remote
Port
Default (0BF5/3061) Valid range: 0000 - FFFF.
|____|____|____|____|
[105] Ethernet Receiver 1 UDP Local
Port
Default (0BF4/3060)Valid range: 0000 - FFFF.
|____|____|____|____|
[106] Ethernet Receiver 1 Domain Name
Default ( ) 32 ASCII characters.
Programming not permitted on UL/ULC listed system.
________________________________
Ethernet Receiver 2 Options
[111] Ethernet Receiver 2 Account Code
Default (0000000000)
Valid range: 0000000001 - FFFFFFFFFE.
|____|____|____|____|____|____|____|____|____|____|
[112] Ethernet Receiver 2 DNIS
Default (000000) Valid range: 000000 - 0FFFFF.
|____|____|____|____|____|____|
[113] Ethernet Receiver 2 Address
Default (000.000.000.000)
|____|____|____||____|____|____||____|____|____||____|____|____|
[114] Ethernet Receiver 2 UDP Remote
Port
Default (0BF5/3061) Valid range: 0000 - FFFF.
|____|____|____|____|
[115] Ethernet Receiver 2 UDP Local
Port
Default (0BF9/3065) Valid range: 0000 -FFFF.
|____|____|____|____|
[116] Ethernet Receiver 2 Domain Name
Default ( )
Programming not permitted on UL/ULC listed system.
____________________________________
Ethernet Options
[124] Ethernet Test Transmission Time
Default (9999) Valid: 00-23(HH); 00-59(MM)
|____|____|____|____|
[125] Ethernet Test Transmission Cycle
Default (000000)
Valid range: 000000 - 999999 minutes.
|____|____|____|____|____|____|
Receiver Diagnostic Testing
[901] Diagnostic Test Transmission
|___| [1] Ethernet 1 Default (OFF).
|___| [2] Ethernet 2 Default (OFF).
System Information (Read Only)
[983] Firmware Update Diagnostics
Section
[984] Communicator Status
[987] Language Version
firealarmresources.com

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Tyco DSC TL280 and is the answer not in the manual?

Tyco DSC TL280 Specifications

General IconGeneral
BrandTyco
ModelDSC TL280
CategoryCell Phone
LanguageEnglish

Related product manuals