COMMISSIONING
47
7.3 TERMINAL BOARD CONNECTIONS
NOTES:
1. SHIELDED TWISTED PAIR, MAXIMUM
DISTANCE 3000m.
MAXIMUM DISTANCE USING MICC
IS 1200m.
EXAMPLES ARE BELDEN 9460 OR
9574.
ACTUAL DISTANCE IS DEPENDANT
ON BAUD RATE, CABLE TYPE AND GAUGE.
2. CATEGORY 5 CABLE.
EXAMPLE, BT CABLE.
3. SHIELDED DATA CABLE.
EXTERNAL
SUPPLY 15 - 30V
4 - 20mV
0V
RS485+
RS485-
MODBUS
RS485+
RS485-
COMMISSIONING
VIDEO OUT +
VIDEO OUT -
{
NOTE 1
{
NOTE 2
{
{
NOTE 3
TB1
S300 RELAY / 4 - 20mA
FIELDBUS TERMINAL PCB
24V
4 - 20
0v
0v
FB+
FB-
EXC+
EXC-
VID+
VID-
10
24V IN
0V
24V OUT
0V OUT
WALK TEST
FAULT N/C
FAULT COM
REMOTE LED
ALARM N/O
ALARM COM
SCREEN IN
SCREEN OUT
TB2
24V
WT
0V
FLT
FLTC
ALED
ALM
ALMC
SCRI
SCRO
20
FAULT N/C
FAULT COM
ALARM N/O
ALARM COM
R
EOL
POSSIBLE MONITORING
CIRCUIT FOR RELAY
VERSION
Fig. 30 Simplified Wiring Diagram
www.acornfiresecurity.com
www.acornfiresecurity.com