TFP963
Page 6 of 8
NOTE:
NOTE:
CONTACT RATINGS:
SWITCH TERMINAL CONNECTIONS
IMPROPER CONNECTION METHOD PROPER CONNECTION METHOD
CAUTION:
For supervised circuits, see "Switch Terminal Connections" above. The Waterow Alarm
Switch has two switches, one can be used to operate a central station, proprietary or remote
signaling unit, while the other contact is used to operate a local audible or visual annunciator.
When connecting to a
UL Listed control panel,
use panel resistor rating
for circuit supervision
Two sets of SPDT (Form C)
10.0 Amps at 125/250VAC
2.0 Amps at 30VDC Resistive
10 mAmps min. at 24VDC
An uninsulated section of a
single conductor is not
permitted to be looped around
the terminal and serve as two
separate connections. The
wire must be severed to serve
as two separate connections,
thereby providing supervision
of the connection in the event
that the wire becomes
dislodged from the terminal.
NO NC COM COM NONC
WIRE NUT
FIRE PANEL OR
ADDRESSABLE
MODULE
WIRE NUT
LOCAL
AUDIBLE/VISUAL
ANNUNCIATOR
BLACKWHITE
NEUTRAL
WHITE
BLACK
(LINE/HOT)
CIRCUIT
BREAKER
LOAD OUT TO
AUDIBLE/VISUAL
ANNUNCIATOR
INCOMING
OUTGOING
SINGLE
CONDUCTOR
UNINSULATED
LOOPED SECTION
CLAMPING
PLATE
TERMINAL
SEPARATE
CONDUCTORS
CLAMPING
PLATE
TERMINAL
SEVERED
STRIPPED
ENDS
FIGURE 6
MODEL RM-1 COMMERCIAL AND RESIDENTIAL RISER MANIFOLD
WIRING GUIDANCE