Operating and mounting manual (translation)
EV / EVF
_______________________________________________________________________________________________________
220.100.091-05 Page 2 /21 Version: 06/2017
TM 4474
1.0 General Remarks
This operating manual includes instructions to assemble and operate the valve in the prescribed and
safe way. Additionally, the adeqaute operating instructions of each special solenoid drive must
be considered.
Series MG... 220.000.038
Series MG...X 220.000.040
Series MG…Xme 220.000.039
If any difficulties appear that can not be solved by means of the operation instructions, further
information may be demanded from the manufacturer.
This operating manual is in accordance with the relevant valid EN safety standards and the valid
prescriptions and rules of the Federal Republic of Germany.
If the solenoids are used abroad of the FRG, the operator and/or the person who is responsible for the
plant concept must take care that the valid national rules are met. The manufacturer reserves the right
of any technical change and improvement. The use of these operating instructions suppose the
qualification of the user according to paragraph 2.3 “qualified staff”.
The operating staff must be trained in accordance with the operating instructions. The operating
manual must always be available at the location where used.
1.1 Valve data
Manufacturer:
UNI Geräte E. Mangelmann
Elektrotechnische Fabrik GmbH
Holtumsweg 13
D-47652 Weeze
Telefon: +49 (0) 2837/9134-0
Fax: +49 (0) 2837/1444
E-Mail: info@uni-geraete.de
Homepage: www.uni-geraete.de
Designation
Directly functioning, currentless closed, spring safety shut off valve with magnet drive.
Type test acc. to DIN EN 264
Working pressure: 5 EV(F) 5bar
10 EV(F) 10bar
25 EV(F) 25bar
40 EV(F) 40bar
Ambient temperature: -10°C to + 60°C (263K to 333K)
Medium temperature: EV -10°C bis + 140°C (263K bis 413K)
EVF -10°C bis + 200°C (263K bis 473K)
Working pressure: 100-EVF 5 / 7 16bar
Medium temperature: -20°C to + 60°C (253K to 333K)
Ambient temperature: -20°C to + 60°C (253K to 333K)
Fitting position: vertical drive ± 5°, with order supplement „W“ vertical or
horizontal.
Working pressure: 100-EVF 10N 100bar
Medium temperature: -10°C to + 60°C (263K to 333K)
Ambient temperature: -10°C to + 60°C (263K to 333K)
Fitting position: vertical drive
Switching cycles: see operating instructions solenoid drive