37
10
DIFFICULT
TN: Check the ue draught or the ue gas
thermostat
TFS: Check the operation of the fan and
its pressure switch .
Any ue obstructions. Make sure the ue
gas exhaust collector is not present with
longer lengths than the manufacturer limit.
No gas or failed burner ignition
Check the gas supply and that the ignition/
detection electrode is working properly.
Pressure shut-off valves.
PARASITE FLAME
Flame detected upon ignition
Check the wiring of the Ign/Det. electrode
and remove any oxidation, press the un-
block key, if the anomaly persists, replace
the electrode.
16 INTERNAL ERROR Replace the electronic board
Power supply voltage too low
19 ERROR
CONFLICT
FIRMWARE
Replace the electronic board
20 ERROR
CIRCUIT
FLAME
Replace the electronic board
21 ERROR
DRIVER VALVE
GAS
Replace the electronic board
ERROR
MEMORY
INTERNAL
Replace the electronic board
ERROR
RESET BUTTON ALWAYS ACTIVE
Check if the button is jammed or glued to
the board.
REMOTE RESETS
The error code appears after 5 resets in
15 minutes
Disconnect and connect voltage to delete
the error code.