BOILERSWITHFORCEDDRAUGHT
In the event the unblock button is NOT pressed,
after10minutestheboilerinanycasereattempts
the ignition cycle.
BOILERSWITHNATURALDRAUGHT
After the sensor has cooled, unblock the boiler by
pressing the unblock key.
It is strictly forbidden to tamper
.
p disclaims any
liability for damage caused as a
result of improper installation, use,
appliance conversion or for non-
compliance with the instructions
supplied by the manufacturer or
installation regulations in force
concerning the material in question.
Whentheboilerdetectsanoperationanomalyor
it is blocked due to a permanent fault, the control
panel display lights up, and the symbol (
) starts
toash.
If the fault is permanent, the error code is displayed
in place of the degrees centigrade.
For the codes listed on this page,
it is not necessary to press button
to display the error code.
by pressing the unblock button “”
thecodethatidentiesthecauseis
displayed,ashing,inplaceofthe
degrees centigrade,
(forthe“errorcodes”listseepar.
4.6 installation and maintenance
instruction manual).
The user can intervene to restore proper operation
only in the following cases:
System pressure too
low
-
Restore the correct pressure value
byactingontheboilerllingvalve
(for optimum operation, the pres-
sure value should be within 0.8
and1bar).
Whentheminimumpressurevalue
is reached (0.6 bar), boiler opera-
tion is resumed.
If water pressure must be con-
tinually restored, contact an
Authorised Unical Assistance
Burner blocking device triggered
due to:
- no gas
- air in pipe (when system is new
or after long idle period).
eliminate the
Check that the gas valve is open
and press the unblock button to
resume the proper operation of
the boiler.
After 3 interventions of the boiler
-
sume operation of the boiler by
Safety thermostat intervention
-
inate the
Bleed the air from the radiators and
restore system pressure.
For all the other error codes, the user is NOT
authorised to resume boiler operation by him-