14
2.5.1 - DATA ACCORDING TO ErP DIRECTIVE
KON 100 KON 115
Element Symbol Unit
E󰀨ective nominal output
Pnominale
kW 99 112
Seasonal energy e󰀩ciency to heat
the room
ƞ
s % 94 92
󰀩
discharge
A A

Useful Heat Output in high-tempera-
ture regime
(Tr 60 °C / Tm 80 °C)
P
4 kW 98,8 111,5
Useful e󰀩ciency at nom. heat output
in high-temperature regime
(Tr 60 °C / Tm 80 °C
ƞ
4 % 89,0 87,4
Useful heat output at 30% of nom.
heat output in low-temperature
regime (Tr 30 °C)
P
1 kW 32,2 37
Useful e󰀩ciency at 30% of nom. heat
output in low-temperature regime
(Tr 30 °C)
ƞ
1 % 98,5 96,7
Range-rated boiler: YES / NO NO NO
Auxiliary electricity consumption
At full load elmax kW 0,289 0,314
At part load elmin kW 0,156 0,160
In stand-by mode P
SB kW 0,018 0,028
Other items
Heat loss in stand-by P
stb kW 0,641 0,642
Emissions of nitrogen oxides ref. PCI (PCS)
NOx
Mg/kWh
43 (39) 47 (42)
Annual electricity consumption Q
HE GJ 301 349
For CH & DHW production boilers
Declarerd load prole - -
Energy e󰀩ciency in DHW production
mode
ƞ
wh % - -
Daily electricity consumption Qelec kWh - -
Daily fuel consumptionl Qfuel kWh - -
Inside sound power level Lwa dB (A) - -
Annual electricity consumption AEC kWh
Annual fuel consumption AFC GJ
󰀩
in DHW production mode
- -
*
