Unical KON 100 - Measurement of Combustion Efficiency During Installation

Unical KON 100
44 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
26
WARNING!
Remove the cap 2,
Insert the probe analysis
of CO2 in the cap hole 3
ATTENTION!
Function reserved for Authorised Assistance
Centres only.
1 
Press the key + (PLUS) and - (MINUS) for at least 3
seconds: boiler at max power, symbol light .
3 MINIMUM OUTPUT
Press key - (MINUS)
boiler at mimum power, symbol ashing.
4 DISABLING
After calibration, press the + (PLUS) and - (MINUS) at the
same time, the symbol o󰀨.
Flue gas
probe
To determine the combustion e󰀩ciency
one must make the following measurements:
- measurement of the combustion air temperature
- measurement of the ue gas temperature and content of
CO
2
taken in the relevant hole 2.

conditions (see par. 3.11.1).
3.11 - MEASUREMENT OF COMBUSTION
EFFICIENCY DURING INSTALLATION
3.11.1- ACTIVATION OF THE CALIBRATION FUNCTION
3.11.2 - POSITIONING THE PROBES