JZ20-UA24 / JZ20-J-UA24 / JZ20-UN20 / JZ20-J-UN20
Sensor is not connected to input, or value exceeds the maximum value
Sensor value is under the minimum value
(JZ20-UA24 / JZ20- J-UA24 only)
12-bit sign(8192 units) for ±10V
12-bit (4096 units) for 4-20mA
Synchronized to scan time.
1kΩ minimum—voltage
500Ω maximum—current
LED, yellow-green, software controlled
(LCD backlight; enables the display to be viewed in the dark)
2 lines, 16 characters long
16 keys, including 10 user-labeled keys
Metal dome, sealed membrane switch
Slides may be installed in the operating panel faceplate to
custom-label the keys and logo picture. An extra logo slide is
included. A complete set of blank slides is available by separate
order.
1.5 µSec for bit operations (typical)
Memory integers (registers),
16 bit
60 user-designed displays available
-200 to 1300˚C (-328 to 3214˚F)
200 to 1820˚C (300 to 3276˚F)
0 to 1768˚C (32 to 3214˚F)
-200 to 750˚C (-328 to 1382˚F)
0 to 1768˚C (32 to 3214˚F
-200 to 760˚C (-328 to 1400˚F)
-200 to 400˚C (-328 to 752˚F)
-200 to 1250˚C (-328 to 2282˚F)
10. The input analog value represents the temperature value as follows:
Analog Value: 260 Actual measured temperature: 26.0C
11. The analog value can indicate faults as shown below: