UMI-B1 UL Series Inverter Fault tracking
104
7. The overvoltage stall
protection is not open.
interference.
7. Check the setting of
relative function codes.
Over-voltage
when acceleration
1. The input voltage is
abnormal.
2. There is large energy
feedback.
3. No braking
components.
4. Braking energy is not
open
1. Check the input power
2. Check if the DEC time
of the load is too short or
the inverter starts during
the rotation of the motor
or it needs to increase the
energy consumption
components.
3. Install the braking
components.
4. Check the setting of
relative function codes.
Over-voltage
when deceleration
Over-voltage
when constant
speed running
1. The voltage of the
power supply is too low.
2. The overvoltage stall
protection is not open.
1. Check the input power
of the supply line.
2. Check the setting of
relative function codes.
1. The voltage of the
power supply is too low.
2. The motor setting rated
current is incorrect.
3. The motor stall or load
transients is too strong.
1. Check the power of the
supply line
2. Reset the rated current
of the motor
3. Check the load and
adjust the torque lift
1. The acceleration is too
fast
2. Reset the rotating
motor
3. The voltage of the
power supply is too low.
4. The load is too heavy.
5. Close loop vector
control, reverse direction
of the code panel and
long low-speed operation
1. Increase the ACC time
2. Avoid the restarting
after stopping.
3. Check the power of the
supply line
4. Select an inverter with
bigger power.
5. Select a proper motor.
The inverter will report
overload pre-alarm
according to the set
value.
Check the load and the
overload pre-alarm point.
Phase loss or fluctuation