Note:
1. The inverter with plastic casing should be
installed in metal distribution cabinet, which
conforms to IP20 and of which the top conforms
to IP3X.
2. Install device in pollution degree 2
environment
Optional filter: meet the degree requirement of
IEC61800-3 C2, IEC61800-3 C3
1PH&3PH 240V: Used in Canada only:
"Transient surge suppression shall be installed
on the line side of this equipment and shall be
rated 240V (phase to ground), 240V (phase to
phase), suitable for overvoltage category III, and
shall provide protection for a rated impulse
withstand voltage peak of 4kV" or equivalent.
3PH: Used in Canada only: "Transient surge
suppression shall be installed on the line side of
this equipment and shall be rated 480V (phase
to ground), 480V (phase to phase), suitable for
overvoltage category III, and shall provide
protection for a rated impulse withstand voltage
peak of 6kV" or equivalent.