UMI-B1 UL Series Inverter Keypad operation procedure
26
4.3.2 How to set the password of the inverter
UMI-B1 UL series inverters provide password protection function to users. Set P7.00 to
gain the password and the password protection becomes valid instantly after quitting
from the function code editing state. Press PRG/ESC again to the function code editing
state, "0.0.0.0.0" will be displayed. Unless using the correct password, the operators
cannot enter it.
Set P7.00 to 0 to cancel password protection function.
The password protection becomes effective instantly after retreating from the function
code editing state. Press PRG/ESC again to the function code editing state, "0.0.0.0.0"
will be displayed. Unless using the correct password, the operators cannot enter it.
Figure 4-4 Sketch map of password setting
4.3.3 How to watch the inverter state through function codes
UMI-B1 UL series inverters provide group P17 as the state inspection group. Users can
enter into P17 directly to watch the state.
Figure 4-5 Sketch map of state watching