UMI-B1 UL Series Inverter Function parameters
28
Function
code
Name
Detailed instruction of parameters
Default
value
Modify
speed and torque. It does not need to install
pulse encoder.
2: SVPWM control
2 is suitable in applications which do not need
high control accuracy, such as the load of fan
and pump. One inverter can drive multiple
motors.
P00.01
Run
command
channel
Select the run command channel of the
inverter.
The control command of the inverter includes:
start, stop, forward/reverse rotating, jogging
and fault reset.
0: Keypad running command channel
("LOCAL/REMOT" light off)
Carry out the command control by RUN,
STOP/RST on the keypad.
Set the multi-function key QUICK/JOG to
FWD/REVC shifting function (P07.02=3) to
change the running direction; press RUN and
STOP/RST simultaneously in running state to
make the inverter coast to stop.
1: Terminal running command channel
("LOCAL/REMOT" flickering)
Carry out the running command control by
the forward rotation, reverse rotation and
forward jogging and reverse jogging of the
multi-function terminals
2: Communication running command channel
("LOCAL/REMOT" on);
The running command is controlled by the
upper monitor via communication
0
P00.03
Max.
output
frequency
This parameter is used to set the maximum
output frequency of the inverter. Users need
to pay attention to this parameter because it
is the foundation of the frequency setting and
the speed of acceleration and deceleration.
Setting range: P00.04400.00Hz
60.00Hz
P00.04
Upper limit
of the
The upper limit of the running frequency is the
upper limit of the output frequency of the
60.00Hz