0: Decelerate to stop: after the stop command
becomes valid, the inverter decelerates to
reduce the output frequency during the set
time. When the frequency decreases to 0Hz,
the inverter stops.
1: Coast to stop: after the stop command
becomes valid, the inverter ceases the output
immediately. And the load coasts to stop at
the mechanical inertia.
Starting frequency of DC braking: start the DC
braking when running frequency reaches
starting frequency determined by P1.09.
Waiting time before DC braking: Inverters
blocks the output before starting the DC
braking. After this waiting time, the DC
braking will be started so as to prevent
over-current fault caused by DC braking at
high speed.
DC braking current: the value of P01.11 is the
percentage of rated current of inverter. The
bigger the DC braking current is, the greater
the braking torque is.