and is detected during the time set by P01.17,
the inverter will stop; otherwise, the inverter
stops in the time set by P01.24.
When the running command channel is the
terminal control, the system will detect the
state of the running terminal during powering
on.
0: The terminal running command is invalid
when powering on. Even the running
command is detected to be valid during
powering on, the inverter won't run and the
system keeps in the protection state until the
running command is canceled and enabled
again.
1: The terminal running command is valid
when powering on. If the running command is
detected to be valid during powering on, the
system will start the inverter automatically
after the initialization.
Note: This function should be selected with
cautions, or serious result may follow.
This function code determines the running
state of the inverter when the set frequency is
lower than the lower-limit one.
0: Run at the lower-limit frequency
1: Stop
2: Hibernation
The inverter will coast to stop when the set
frequency is lower than the lower-limit one.if
the set frequency is above the lower limit one