UMI-B1 UL Series Inverter Function parameters
46
Function
code
Name
Detailed instruction of parameters
Default
value
Modify
P03.19
Upper-limit
setting of
braking
torque
(P03.20 sets P03.18 and P03.21 sets
P03.19)
1: Analog AI1 setting upper-limit torque
2: Analog AI2 setting upper-limit torque
3: Analog AI3 setting upper-limit torque
4: Pulse frequency HDI setting upper-limit
torque
5: MODBUS communication setting
upper-limit torque
68: Reserved
Note: Setting mode 18, 100% corresponds
to three times of the motor current.
0
P03.20
Electromot
ion
torque
upper-limit
keypad
setting
The function code is used to set the limit of
the torque.
Setting range: 0.0300.0% (motor rated
current)
180.0%
P03.21
Braking
torque
upper-limit
keypad
setting
180.0%
P03.22
Weakenin
g
coefficient
in constant
power
zone
The usage of motor in weakening control.
Function code P03.22 and P03.23 are
effective at constant power. The motor will
enter into the weakening state when the
motor runs at rated speed. Change the
weakening curve by modifying the weakening
control coefficient. The bigger the weakening
control coefficient is, the steeper the weak
curve is.
Setting range of P03.22: 0.12.0
Setting range of P03.23: 10%100%
0.3
P03.23
The lowest
weakening
point in
constant
power
zone
20%
P03.24
Max.
voltage
limit
P03.24 set the Max. Voltage of the inverter,
which is dependent on the site situation.
Setting range: 0.0120.0%
100.0%