UMI-B1 UL Series Inverter Function parameters
51
Function
code
Name
Detailed instruction of parameters
Default
value
Modify
Vmax
Vmin
Vset
t1 t2
Time
t1=P04.29
t2=P04.30
P04.33
Weakeni
ng
coefficien
t in
constant
power
zone
Adjust the output voltage of the inverter in
SVPWM mode when weakening.
Note: Invalid in the constant torque mode.
Output Voltage
Output frequency
V
out
V
b
f
b
2f
b
(P04.33-1.00) x V
b
Setting range of P04.33: 1.001.30
1.00
P05 Group Input terminals
P05.00
HDI input
selection
0: HDI is high pulse input. See
P05.49P05.54
1: HDI is switch input
0
P05.01
S1
terminals
function
selection
Note: S1S4, HDI are the upper terminals on
the control board and P05.12 can be used to
set the function of S5S8
0: No function
1: Forward rotation operation
2: Reverse rotation operation
3: 3-wire control operation
4: Forward jogging
5: Reverse jogging
6: Coast to stop
7: Fault reset
8: Operation pause
9: External fault input
10: Increasing frequency setting (UP)
11: Decreasing frequency setting (DOWN)
12: Cancel the frequency change setting
1
P05.02
S2
terminals
function
selection
4
P05.03
S3
terminals
function
selection
7
P05.04
S4
terminals
function
selection
0