UMI-B1 UL Series Inverter Function parameters
53
Function
code
Name
Detailed instruction of parameters
Default
value
Modify
of the input
terminals
Set the bit to 0, the input terminal is anode.
Set the bit to 1, the input terminal is cathode.
BIT8
BIT7
BIT6
BIT5
BIT4
HDI
S8
S7
S6
S5
BIT3
BIT2
BIT1
BIT0
S4
S3
S2
S1
The setting range: 0x0000x1FF
P05.11
Switch
filter time
Set the sample filter time of S1S4 and HDI
terminals. If the interference is strong,
increase the parameter to avoid wrong
operation.
0.0001.000s
0.010s
P05.12
Virtual
terminals
setting
0x0000x1FF (0: Disabled, 1:Enabled )
BIT0: S1 virtual terminal
BIT1: S2 virtual terminal
BIT2: S3 virtual terminal
BIT3: S4 virtual terminal
BIT4: S5 virtual terminal
BIT5: S6 virtual terminal
BIT6: S7 virtual terminal
BIT7: S8 virtual terminal
BIT8: HDI virtual terminal
0x000
P05.13
Terminals
control
running
mode
Set the operation mode of the terminals
control
0: 2-wire control 1, comply the enable with the
direction. This mode is widely used. It
determines the rotation direction by the
defined FWD and REV terminals command.
FWD
REV
COM
K1
K2
Running
command
FWD REV
OFF OFF
OFF
OFF
ON
ON
ON ON
Stopping
Hold on
Forward
running
Reverse
running
1: 2-wire control 2; Separate the enable from
the direction. FWD defined by this mode is
the enabling ones. The direction depends on
the state of the defined REV.
0