UMI-B1 UL Series Inverter Function parameters
83
Detailed instruction of parameters
P10 Group Simple PLC and multi-step speed control
0: Stop after running once. The inverter has
to be commanded again after finishing a
cycle.
1: Run at the final value after running once.
After finish a signal, the inverter will keep the
running frequency and direction of the last
run.
2: Cycle running. The inverter will keep on
running until receiving a stop command and
then, the system will stop.
Simple
PLC
memory
selection
0: Power loss without memory
1: Power loss memory; PLC record the
running stage and frequency when power
loss.
100.0% of the frequency setting corresponds
to the Max. Frequency P00.03.
When selecting simple PLC running, set
P10.02–P10.33 to define the running
frequency and direction of all stages.
Note: The symbol of multi-step determines
the running direction of simple PLC. The
negative value means reverse rotation.
P10.02
P10.04
P10.06
P10.32
P10.30
P10.28DEC time
(2 stages)
ACC time
(2 stags)
P10.03 P10.05 P10.07 P10.31 P10.33
multi-step speeds are in the range of
--f
max
–f
max
and it can be
UMI-B1 UL series inverters can set 16 stages
speed, selected by the combination of
multi-step terminals 1–4, corresponding to
the speed 0 to speed 15.
The
running
time of
stage 0
The
running
time of
stage 1
The
running
time of
stage 2