UMI-B1 UL Series Inverter Function parameters
92
Function
code
Name
Detailed instruction of parameters
Default
value
Modify
address
0; the broadcast address is the
communication address. All slaves on the
MODBUS fieldbus can receive the frame, but
the salve doesn't answer.
The communication address of the inverter is
unique in the communication net. This is the
fundamental for the point to point
communication between the upper monitor
and the inverter.
Note: The address of the slave cannot set to
0.
P14.01
Communic
ation baud
ratio
Set the digital transmission speed between
the upper monitor and the inverter.
0: 1200BPS
1: 2400BPS
2: 4800BPS
3: 9600BPS
4: 19200BPS
5: 38400BPS
6: 57600BPS
Note: The baud rate between the upper
monitor and the inverter must be the same.
Otherwise, the communication is not applied.
The bigger the baud rate, the quicker the
communication speed.
4
P14.02
Digital bit
checkout
The data format between the upper monitor
and the inverter must be the same.
Otherwise, the communication is not applied.
0: No check (N,8,1) for RTU
1: Even check (E,8,1) for RTU
2: Odd check (O,8,1) for RTU
3: No check (N,8,2) for RTU
4: Even check (E,8,2) for RTU
5: Odd check (O,8,2) for RTU
6: No check (N,7,1) for ASCII
7: Even check (E,7,1) for ASCII
8: Odd check (O,7,1) for ASCII
9: No check (N,7,2) for ASCII
10: Even check (E,7,2) for ASCII
1