EasyManua.ls Logo

Unitronics V200-18-E1B - Technical Specifications; Digital Inputs Specifications; Relay Outputs Specifications

Unitronics V200-18-E1B
7 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Installation Guide
6
Unitronics
V200-18-E1B Technical Specifications
Digital Inputs
Number of inputs
16 (in two groups)
Input type
pnp (source) or npn (sink), set by wiring.
Galvanic isolation
Yes
Nominal input voltage
24VDC
Input voltage
pnp (source)
0-5VDC for Logic ‘0’
17-28.8VDC for Logic ‘1’
npn (sink)
17-28.8VDC for Logic ‘0’
0-5VDC for Logic ‘1’
Input current
6mA@24VDC for inputs #4 to #15
8.8mA@24VDC for inputs #0 to #3
Response time
10mSec typical
High speed inputs
Specifications below apply. See Notes 1 and 2.
Resolution
32-bit
Frequency
10kHz maximum
Minimum pulse width
40μs
Notes:
1. Inputs #0 and #2 can each function as either high-speed counter or as part of a shaft encoder. In each case, high-speed
input specifications apply. When used as a normal digital input, normal input specifications apply.
2. Inputs #1 and #3 can each function as either counter reset, or as a normal digital input; in either case, its specifications are
those of a normal digital input. These inputs may also be used as part of a shaft encoder. In this case, high-speed input
specifications apply.
Relay Outputs
Number of outputs
10. See Note 3.
Output type
SPST-NO relay (Form A)
Isolation
By relay
Type of relay
Panasonic JQ1AP-24V, or compatible
Output current
5A maximum (resistive load ).
8A maximum for common signal. See Note 3.
Rated voltage
250VAC / 30VDC
Minimum load
1mA@5VDC
Life expectancy
50k operations at maximum load
Reponse time
10mS (typical)
Contact protection
External precautions required. See Increasing Contact Life Span, page 5.
Outputs’ power supply
Nominal operating voltage
24VDC
Operating voltage
20.4 to 28.8VDC
Max. current consumption
90mA@24VDC
Notes:
3. Outputs #1, #2, #3, and #4 share a common signal. All other outputs have individual contacts.