7.1 95-8533
A-1
APPENDIX A
FM APProvAl DEscrIPtIoN
HAZARDOUS LOCATIONS
•RefertoFiguresA-1andA-2forSystemClassificationdetails.
•EQxxxxEMversionsratednonincendiveforClassI,Div.2,GroupsA,B,C,D(T4A).
FIRE DETECTION & RELEASING
•National Fire Alarm Code performance verified per ANSI/NFPA 72-2002. Refer to Table A-1 for supervision
characteristics.
•Refer to the Model X3301, X5200, X2200 and X9800 manuals (see Table 2-4) for further FM flame performance
details.Additional2secondresponsetimeappliedforsystemcommunication.
•ModelsEQ3700SeriesandEQ22xxARMSeriesareApprovedasagentreleasingcircuitsandareApprovedforuse
withthefollowingautomaticdelugeandpre-actionsolenoids:
GAS DETECTION
•Combustible Gas Performance verified for 0 to 100% LFL methane-in-air atmospheres per FM 6310/6320.
Accuracy: ±3%LFL from0to 50% LFL, ±5% LFLfrom51% to 100% LFL. For theModel PIRECL,referto the
PIRECLmanual(formnumber95-8526)forfurtherFMgasperformancedetails.
NOTE:
Detector Electronics combustible gas detection K factors are not FM veried.
•H
2
SToxicGasPerformanceverified0to20,50or100ppmperFMrequirements.Accuracy:±2ppmfrom0to20
ppm,±10%ofconcentrationfrom21to100ppm.ModelsC7064E4012andC7064E5012HydrogenSulfide(H2S)
SensorsExplosion-proofforClassI,Div.1,GroupsCandDHazardous(Classified)LocationsperFM3615.Model
C7064E5014HydrogenSulfide(H2S)SensorsExplosion-prooffor ClassI,Div.1,GroupsB,CandDHazardous
(Classified)LocationsperFM3615.Operatingtemperaturelimitsare–40°Cto+40°C.
NOTE:
Sensor cross sensitivity has not been veried by FM.
•Calibration of the above listed sensors has been FM verified using the respective EQ22xxDCU, EQ22xxDCUEX,
andPIRECLwiththeDet-Tronics225130-001(50%LFLmethane)and/or227115-001H2SCalibrationKits.
•TheEQ22xxDCUSeriescanbeusedwithanyFMApproved4-20madevice.
NOTE
FM Approval of the 4-20 ma input does not include or imply approval of the gas detection apparatus such as
sensors, transmitters, or devices connected to the system. In order to maintain FM Approval of the system, all
4-20 ma gas detection instruments connected to the input must also be FM Approved.
FM Solenoid Group Manufacturer Model
B ASCO T8210A107
D ASCO 8210G207
E Skinner 73218BN4UNLVNOC111C2
F Skinner 73212BN4TNLVNOC322C2
G Skinner 71395SN2ENJ1NOH111C2
H Viking HV-274-0601

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the UTC Fire and Security DET-TRONICS 95-8533 and is the answer not in the manual?

UTC Fire and Security DET-TRONICS 95-8533 Specifications

General IconGeneral
BrandUTC Fire and Security
ModelDET-TRONICS 95-8533
CategoryController
LanguageEnglish