7.1 95-85332-10
EQ3740IPM Intelligent Protection Module
The IPM
(see Figure 2-13)
is designed to provide
continuous and automated local area fire protection,
while monitoring system operation through continuous
supervision of its Inputs/Outputs and Local Operating
Network/Signalling Line Circuit (LON/SLC) connection to
the EQP controller.
In addition the module contains a unique “embedded
logic program” that if enabled during configuration
allows the IPM to perform local area protection in a
“back-up mode” without controller interaction.
The IPM utilizes eight pre-configured Input/Output (I/O)
channels to perform its monitoring, supervison and
mitigation functions.
On the input side, three supervised channels provide
connections for an Abort station, a Manual Release
station and a Supervisory device. Two additional input
channels (zones) provide connections for “two-wire”
conventional (non-relay based) smoke and heat
detectors.
On the output side, three supervised outputs provide
connections for a notification appliance such as a
bell, horn or lamp and two releasing circuits for a main
and reserve or secondary agent release.
Each channel on the module is provided with
individual indicators for active and fault conditions.
Refer to the Intelligent Protection Module Specification
Data sheet (form number 90-1184) for additional
information.
EQ25xxARM Agent Release Module
The EQ25xxARM Series Agent Release Module (ARM)
(see Figure 2-14) provides agent release or deluge
pre-action capability. The device is controlled by
programmable logic in the Controller. Time delay,
abort and manual release sequences allow the device
output to be programmed for use in unique
applications.
The device is field programmed to operate in one of
the following modes:
Squib– Output is activated for a factory-set
time period to set off the explosive
device.
Timed– Output is activated for a field
selectable duration from 1 to 65,000
seconds.
Continuous– Output latches until reset.
Non-latching– Output follows the input.
The device can monitor and control two output
devices (24 vdc rated) that are programmed and
energized together. The release circuits are
compatible with a variety of solenoid or initiator
(squib) based suppression systems.
The release circuit is supervised for open circuit
conditions. If a trouble condition occurs (open circuit
or solenoid supply voltage less than 19 volts), it will
be indicated at the Controller. Each output is rated at
2 amperes and auxiliary input terminals are provided
for additional 24 vdc output power where needed.
NOTE
For deluge and pre-action applications, the input
voltage to the ARM or DCIO must be 21 VDC
minimum with connection to any solenoid listed
in Table 2-6 or 2-7. Wiring must be in accordance
with the listed maximum wiring lengths.
Refer to the EQ25xxARM Specification Data sheet
(form number 90-1128) for additional information
Figure 2-13—Intelligent Protection Module

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the UTC Fire and Security DET-TRONICS 95-8533 and is the answer not in the manual?

UTC Fire and Security DET-TRONICS 95-8533 Specifications

General IconGeneral
BrandUTC Fire and Security
ModelDET-TRONICS 95-8533
CategoryController
LanguageEnglish