ENGLISH
39
PARAMETER VALUE DESCRIPTION DEFAULT MEMO
Pot
Motor power
60
30 - 1 00
The displayed value is the percentage of max. motor power
SPun
Start off
When the door is standstill and it begins moving, the initial inertia
must be faced, therefore, if your door is quite heavy, it could not move.
In case the SPUNTO (pickup) function is activated, for the first 2 seconds
of motion of each door, the control unit will ignore
Potvalue and it will
give motor the maximum power command in order to overcome the
d
oor inertia.
no
no
Function deactivated
Si
Function activated
t.P.So
Soft start (slowed down)
1 .5”
no
Function deactivated
0. 5” - 30”
During the first seconds of motion of the door, the control unit will give
motor a reduced power command, for a softer start.
(adjustable time from 0,5 a 30 seconds)
t.rA L
Slowing down time
6. 0”
no
Function deactivated
0. 5” - 22.5”
During the last seconds of motion, the control unit will give motor a
reduced power command, to avoid a strong impact with the stop end
t.A P is the max. allowed time
m WARNING: In case the self-learning function of working times is
NOT used, we recommend disabling the slowing down function in order to
measure both opening and closing times, and to enable it again once the
setup has been carried out. The control unit will automatically consider the
working time delay caused by the slowing down.
St.A P
Start command during the opening phase
This menu allows fixing the control unit conduct in case it receives a
Start command during the opening phase
PA U S
PA U S
The door stops and goes to pause
C hiu
The door immediately starts closing
no
The door go on with the opening phase (command is ignored)
St.C h
Start command during the closing phase
This menu allows fixing the control unit conduct in case it receives a
Start command during the closing phase
StoP
StoP
The door stops and its cycle is considered as finished
A PEr
The door opens again
St.PA
Start command during the pause
This menu allows fixing the control unit conduct in case it receives a
Start command when the door is open during its pause phase
C hiU
C hiU
The door starts closing
no
Command is ignored
C h.A U
Automatic closing
no
no
Function deactivated
0.5” - 20.0’
The door closes after the setup time