vacon • 14 Installation
Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
4
Protection class IP21: Cut free the opening on the AC drive cover for the Ether-
net cable.
Protection class IP54: Cut the rubber grommets open to slide the cables
through. Should the grommets fold in while inserting the cable, just draw the
cable back a bit to straighten the grommets up. Do not cut the grommet open-
ings wider than what is necessary for the cables you are using.
NOTE! To meet the requirements of the enclosure class IP54, the connection
between the grommet and the cable must be tight. Therefore, lead the first bit of
the cable out of the grommet straight before letting it bend. If this is not possi-
ble, the tightness of the connection must be ensured with insulation tape or a
cable tie.
5
Remount the AC drive cover.
NOTE! When planning the cable runs, remember to keep the distance between
the Ethernet cable and the motor cable at a minimum of 30 cm. See figure below.
9068.emf
IP54
9265.emf
IP21
Ethernet
cable