vacon • 50 APPENDIX 2 - CONTROL AND STATUS WORD
Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
10. APPENDIX 2 - CONTROL AND STATUS WORD
10.1 Control Word bit description
The Control word is composed of 32 bits. FBFixedControlWord consist of the first 16 bits. FBGen-
eralControlWord consist of the remaining 16 bits. While the functionality of FBFixedControlWord is
fixed in the VACON
®
standard applications, the functionality of FBGeneralControlWord is totally
application specific and can vary even in the VACON
®
standard applications.
The meanings of FBFixedControlWord bits are described below. Unused bits have to be set to zero.
NOTE! This table is valid for VACON
®
standard applications. VACON
®
100 HVAC may not support all
functions. See Table 52.
Table 51. Control Word
Bit Function Value Description
0 Start/Stop
0 Stop request from fieldbus.
1 Run request from fieldbus.
1 Direction
0 Requested direction is "FORWARD".
1 Requested direction is "REVERSE".
2Fault reset
0 No action.
1
Rising edge (0->1) = Active faults, alarms and
infos are reset.
3Stop mode 1
0 Stop mode is unmodified.
1 Stop mode is overridden to "Coasting".
4Stop mode 2
0 Stop mode is unmodified.
1 Stop mode is overridden to "Ramping".
5 Quick ramp time
0 Normal deceleration ramp time.
1
Deceleration ramp time is switched to shorter
than normal.
6 Freeze Setpoint
0
Changes in the setpoint value from fieldbus (FB
Speed Reference) are taken into use by the appli-
cation.
1
Changes in the setpoint value from fieldbus (FB
Speed Reference) are not taken into use by the
application.
7Setpoint to Zero
0
The setpoint value from fieldbus is taken from FB
Speed Reference.
1 The setpoint value from fieldbus is changed to 0.
8
Request Fieldbus
Control
0
Control Place is as parameterized in the drive
(unchanged).
1 Control Place is overridden to Fieldbus Control.
9
Request Fieldbus
Reference
0
Source of the setpoint value is as parameterized
in the drive (unchanged).
1
Source of the setpoint value is overridden to
Fieldbus.
10 Jogging 1
0 No action.
1 Jogging request with reference 1.