APPENDIX 2 - CONTROL AND STATUS WORD vacon • 51
Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
10
11 Jogging 2
0 No action.
1 Jogging request with reference 2.
12 Quick stop
0 No action
1 Drive executes quick stop / emergency stop.
13 - 15 Reserved
Table 52. Control word bit support in VACON
®
100 family AC drives
Bit Function
VACON
®
100
INDUSTRIAL / FLOW
VACON
®
100 HVAC
0Start/Stop x x
1 Direction x x
2Fault reset x x
3 Stop mode 1 x x
4 Stop mode 2 x x
5 Quick ramp time x
6 Freeze setpoint x x
7Setpoint to Zero x
8 Request Fieldbus Control x x
9 Request Fieldbus Reference x x
10 Jogging 1 x
11 Jogging 2 x
12 Quick stop x
13-15 Reserved
Table 51. Control Word
Bit Function Value Description