Communications vacon • 31
Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
6
6.3 Modbus data mapping
6.3.1 Coils registers
A "coil" in Modbus is a single-bit binary data item which can be both read and written. In VACON
®
100 family AC drives, the coils refer to some bits in the fieldbus control word." See page 34.
6.3.2 Clearing resettable counters
The VACON
®
AC drives have trip counters for operation days and energy. These counters can be
reset to zero by writing value '1' to addresses defined in table below. You can also use coils defined
in chapter 6.3.1.
6.3.3 Discrete inputs
A "discrete input" in Modbus is a single-bit binary data item which is read-only. In VACON
®
100
family AC drives, the discrete inputs refer to the fieldbus status word bits. See Chapter 10.
Table 16. Defined coil registers
Address Function Purpose
0001 RUN/STOP Control Word, bit 0
0002 Direction Control Word, bit 1
0003 Fault reset Control Word, bit 2
0017 Reset Clears operation days trip counter
0018 Reset Clears energy trip counter
Table 17. Clearing trip counters
Address Function Purpose
40101 Reset Clears operation days trip counter
40301 Reset Clears energy trip counter
Table 18. Defined Input Discrete
Address Function Purpose
10001 Ready Status Word, bit 0
10002 Run Status Word, bit 1
10003 Direction Status Word, bit 2
10004 Fault Status Word, bit 3
10005 Alarm Status Word, bit 4
10006 At reference Status Word, bit 5
10007 Zero speed Status Word, bit 6
10008 Flux ready Status Word, bit 7