6
vacon • 36 Communications
Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
Figure 7. IDMap initialization
Once the IDMap address range has been initialized with any parameter ID number, the parameter
value can be read and written in the IDMap Read/Write address range address IDMap address + 100.
If the IDMap table has not been initialized, all data fields are showing the value '0'. Once the IDMap
table has been initialized, the parameter ID's are stored in the VACON
®
100 family AC drive’s flash
memory.
Example of 32Bit IDMap
6.3.9 Operation day counter
Control unit operating time counter (total value). This counter cannot be reset. The values are read
only.
Table 23. Parameter Values in 16-bit IDMap Read/Write registers
Address Data
10601 Data included in parameter ID700
10602 Data included in parameter ID702
10603 Data included in parameter ID707
10604 Data included in parameter ID704
Table 24. Example of parameter values in 32-bit IDMap Read/Write registers
Address Data
10701 Data High, parameter ID700
10702 Data Low, parameter ID700
10703 Data High, parameter ID702
10704 Data Low, parameter ID702