24 • vacon ELECTRICAL CONNECTION
Tel: +358-201-2121 • Fax: +358-201-212 205
I/O terminals on OPTA1 (coded terminals painted black)
Parameter reference
on keypad and NCDrive
Reference output +10V; Maximum current 10 mA
Selection V or mA with jumper block X1 (see page 25):
Default: 0– +10V (Ri = 200 kΩ)
(-10V..+10V Joy-stick control, selected with ajumper)
0– 20mA (Ri = 250 Ω)
Resolution 0.1%; Accuracy ±1%
AI1– Differential input if not connected to ground;
Allows ±20V differential mode voltage to GND
Selection V or mA with jumper block X2 (see page 25):
Default: 0– 20mA (Ri = 250 Ω)
0– +10V (Ri = 200 kΩ)
(-10V..+10V Joy-stick control, selected with a jumper)
Resolution: 0.1%; Accuracy ±1%
AI2– Differential input if not connected to ground;
Allows ±20V differential mode voltage to GND
24 Vout (bi-
directional)
24V auxiliary voltage output. Short-circuit protected.
±15%, maximum current 150 mA
+24Vdc external supply may be connected.
Galvanically connected to terminal #12.
Ground for reference and controls
Galvanically connected to terminals #13,19.
Digital input 1 (Common CMA); R
i
= min. 5kΩ
Digital input 2 (Common CMA); R
i
= min. 5kΩ
Digital input 3 (Common CMA); R
i
= min. 5kΩ
CMA Digital input common A for DIN1, DIN2 and DIN3.
Connection by default to GND.
Selection with jumper block X3 (see page 25):
Galvanically connected to terminal #6.
GND Same as terminal #7
Galvanically connected to terminals #7 and 19
Digital input 4 (Common CMB); R
i
= min. 5kΩ
Digital input 5 (Common CMB); R
i
= min. 5kΩ
Digital input 6 (Common CMB); R
i
= min. 5kΩ
CMB Digital input common B for DIN4, DIN5 and DIN6.
Connection by default to GND.
Selection with jumper block X3 (see page 25):
Analogue output
Output signal range:
Current 0(4)–20mA, R
L
max 500Ω or
Voltage 0—10V, R
L
>1kΩ
Selection with jumper block X6 (see page 25):
Resolution: 0.1% (10 bits); Accuracy ±2%
Open collector output
Maximum U
in
= 48VDC
Maximum current = 50 mA
Table 5-6. OPTA1 I/O terminals