28 • vacon ELECTRICAL CONNECTION
Tel: +358-201-2121 • Fax: +358-201-212 205
5.3.1
Option board OPTB5
Description:
I/O expander board with three relay outputs.
Allowed slots:
B, C, D, E
Type ID:
16949
Terminals:
Three terminal blocks; Screw terminals (M3); No coding
Jumpers:
None
Board parameters:
None
I/O terminals on OPTB5
Terminal
Parameter reference
Keypad/NCDrive
Technical information
22
23
RO1/common
RO1/normal open
DigOUT:
X.1
Switching capacity 24VDC/8A
250VAC/8A
125VDC/0.4A
Min. switching load 5V/10mA
25
26
RO2/common
RO2/normal open
DigOUT:
X.2
Switching capacity 24VDC/8A
250VAC/8A
125VDC/0.4A
Min. switching load 5V/10mA
28
29
RO3/common
RO3/normal open
DigOUT:
X.3
Switching capacity 24VDC/8A
250VAC/8A
125VDC/0.4A
Min. switching load 5V/10mA
Table 5-9. OPTB5 I/O terminals
Note: This expander board can be placed into four different slots on the control board. Therefore,
the '
X' given in the Parameter reference shall be replaced by the slot letter (B, C, D, or E) depending
on the slot which the expander board is plugged into.