START UP vacon • 37
24-hour support: +358 (0)201 212 575 • Email: vacon@vacon.com
6.1.5.1
Monitoring menu
To enter the Monitoring menu from the Main menu, press the Push button Menu right when the lo-
cation indication
M1 appears in the first line of the screen. The following figure shows how to view
the monitored values.
The monitored signals have the indication V#.# and are listed in the following table. Values are up-
dated every 0.3 seconds.
This menu is used only to verify the signals. Values can not be modified.
Code
Parameter
Min
Max
Unit
ID
Description
V1.1 Output power 0 1000 kW 1707
Output power of inverter, with compensated
LCL filter losses.
V1.2 Total energy kWh 0 4,29E+09 kWh 1837 Total energy of inverter fed into the grid.
V1.3 Energy today kWh 0 6553,5 kWh 1708 Energy fed into the grid today.
V1.4
Energy yesterday
0
6553,5
kWh
1733
Energy fed into the grid yesterday.
V1.5
DC voltage refer-
ence
50 150 % 1200
Used DC voltage reference by the regenerative
unit in % of the nominal DC voltage.
V1.6 DC-link voltage 0 1000 V 1839 Filtered DC-link voltage in Volt.
V1.7 Unit temperature -50 200 °C 1109 Temperature of the unit in Celsius
V1.8 AC voltage 0 1000 V 1709
AC voltage measured on the grid side of the
main contactor by an external measurement
circuit.
V1.9 AC frequency -60 60 Hz 1835
Grid frequency in Hz. The sign indicates the
phase order. Can be monitored only when
UNIT is in RUN state.
V1.10 Output current 0 Varies A 1834
Output current of the inverter coming out of
the cabinet (transformers inside cabinet are
taken into consideration).
V1.11 Run time total [h] 0 99999999 h 1836 Total time the inverter has been running.
V1.12 Run time today 0 255 h 1731 The time the inverter has been running today.
V1.13 Run time yesterday 0 255 h 1732 The time the inverter ran yesterday.
V1.14 Grid connections 0 4,29E+09 1706
Total number of times the inverter has closed
the main contactor and connected to the grid.
V1.15 Standby remaining 0 65535 s 1201
Remaining time in standby mode, if standby
mode is activated.
Table 6-1. Monitoring values
RUN READY
Local
M1
Monitor
V1
V14
RUN READY
Local
V1.1
Output power
19.4 kW
RUN READY
Local
V1.1
Daily energy
125 kWh