MAINTENANCE AND TROUBLESHOOTING vacon • 43
24-hour support: +358 (0)201 212 575 • Email: vacon@vacon.com
MCC Fault
Contactor acknowledgment is used
through digital input and close com-
mand is given without response within
the time set with parameter “MCont
FaultDelay”
Check the main power switch of the
Drive and Acknowledge input.
LCL Tempera-
ture
LCL Overtemp trip from digital input.
Check the LCL filter and signal connec-
tion. Check fan
AC VoltMax Trip
AC voltage on line side is above the max
limit.
Check AC Voltage
AC voltage on line side is below the min
FreqOverLimit
AC frequency on line side is above the
max limit.
Check AC Frequency
FreqUnderLimit
AC frequency on line side is below the
min limit.
Check AC Frequency
DC Ground
Warning
DC Insulation measurement signal has
gone above the warning limit.
Check DC Insulation
DC Ground
Fault
DC Insulation measurement signal has
gone above the fault limit.
Check DC Insulation
Surge Alarm Surge alarm from digital input.
Remove fault situation from external
device.
Fieldbus
Heartbeat signal from touchpad panel is
missing while running in array configu-
ration.
Warning = inverter not active
Fault = inverter active
Check touchpad panel. Check the con-
trol place
Input Switch Input Switch in wrong state Check the input Switch
Table 7-1. Fault codes