Appendix
28 Installation instructions Heat pump control interface module 0020291573_00
Statuscode Meaning
S.133 Domestic hot water:
Prerun
The start conditions for the compressor in domestic hot water mode are checked. Start the other actu-
ators for domestic hot water mode.
S.134 Domestic hot water:
Compressor active
The compressor works in order to meet the domestic hot water demand.
S.135 Domestic hot water:
Immersion heater active
The external back-up heater is used in domestic hot water mode.
S.137 Domestic hot water:
Overrun
The domestic hot water demand is met, the compressor is switched off. The pump and fan overrun.
S.141 Heating: Immersion
heater shutdown
The heat demand is met, the external back-up heater is switched off.
S.142 Heating: Immersion
heater blocked
The external back-up heater is blocked for heating mode.
S.151 Domestic hot water:
Immersion heater shutdown
The domestic hot water demand is met, the external back-up heater is switched off.
S.152 Domestic hot water:
Immersion heater blocked
The external back-up heater is blocked for domestic hot water mode.
S.173 Anti-cycling time for
the energy supply company
The mains voltage supply is interrupted by the energy supply company. The maximum anti-cycling
time is set in the configuration.
S.202 Check programme: Pur-
ging of building circuit active
The building circuit pump is actuated in cyclical intervals, alternately in heating mode and domestic
hot water mode.
S.203 Actuator test active The sensor and actuator test is currently operating.
S.212 Connection fault: Con-
trol not recognised
System control was previously detected but the connection is broken. Check the eBUS connection to
the system control. It can only be operated with the heat pump's additional functions.
S.240 Compr. oil temp. too
low, environment too cold
The compressor heating is switched on. The unit does not start up.
S.252 Fan unit 1: Fan blocked If the fan speed is 0 rpm, the heat pump is switched off for 15 minutes and then restarted. If the fan
does not start up after four unsuccessful restarts, the heat pump is switched off and the fault mes-
sage F.718 is displayed.
S.255 Fan unit 1: Air inlet
temp. too high
The compressor does not start because the outdoor temperature at the fan is above the operating
limits. Heating mode: > 43 °C. Domestic hot water mode: > 43 °C. Cooling mode: > 46 °C.
S.256 Fan unit 1: Air inlet
temp. too low
The compressor does not start because the outdoor temperature at the fan is below the operating
limits. Heating mode: < -20 °C. Domestic hot water mode: < -20 °C. Cooling mode: < 15 °C.
S.260 Fan unit 2: Fan blocked If the fan speed is 0 rpm, the heat pump is switched off for 15 minutes and then restarted. If the fan
does not start up after four unsuccessful restarts, the heat pump is switched off and the fault mes-
sage F.785 is displayed.
S.272 Building circuit: Re-
maining feed head limit active
The remaining feed head that is set under the configuration is reached.
S.273 Building circuit: Flow
temperature too low
The flow temperature that is measured in the building circuit is below the operating limits.
S.275 Building circuit: Flow
rate too low
Building circuit pump defective. All consumers in the heating system are closed. The values fall below
the specific minimum volume flows. Check that the dirt filter is permeable. Check the stopcocks and
thermostatic valves. Ensure that the flow rate is at least 35% of the nominal flow rate. Check that the
building circuit pump functions correctly.
S.276 Building circuit: Lock-
out contact S20 open
Contact S20 is open at the heat pump's main PCB. Incorrect limit thermostat setting. Flow temper-
ature sensor (heat pump, gas-fired boiler, system sensor) measures values that deviate downwards.
Adjust the maximum flow temperature for the direct heating circuit via the system control (observe
the upper switch-off threshold for the boilers). Adjust the set value for the limit thermostat. Check the
sensor values
S.277 Building circuit: Pump
fault
If the building circuit pump is inactive, the heat pump is switched off for 10 minutes and is then restar-
ted. If the building circuit pump does not start up after three unsuccessful restarts, the heat pump is
switched off and the fault message F.788 is displayed.
S.280 Freq. converter fault:
Compressor
The compressor motor or wiring is defective.
S.281 Freq. converter fault:
Mains voltage
There is overvoltage or undervoltage.
S.282 Freq. converter fault:
Overheating
If the cooling of the frequency inverter is not sufficient, the heat pump is switched off for one hour and
then restarted again. If the cooling is not sufficient after three unsuccessful restarts, the heat pump is
switched off and the fault message F.819 is displayed.
S.283 De-icing time too long If the de-icing takes longer than 15 minutes, the heat pump is restarted. If the time for the de-icing is
still not sufficient after three unsuccessful restarts, the heat pump is switched off and the fault mes-
sage F.741 is displayed. Check whether sufficient thermal energy is available from the building cir-
cuit.

Table of Contents

Other manuals for Vaillant VWZ AI

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Vaillant VWZ AI and is the answer not in the manual?

Vaillant VWZ AI Specifications

General IconGeneral
BrandVaillant
ModelVWZ AI
CategoryControl Unit
LanguageEnglish

Related product manuals