DHP-UM-013
Val Controls A/S Limfjordsvej 3 DK-6715 Esbjerg N Tel. +45 7547 0600 Fax +45 7547 0611
vc@valcontrols.com www.valcontrols.com
Revision: 4
9/58
4.2 FF - Function blocks used in Default Setting.
Analogue Input (AI)
Analog input function block, used to receive input data from the transducer blocks (MTB). Other
function blocks can then read the value from the “OUT” port.
In the Default setting:
The “OUT” contains the actual position signal from the Val Controls Device. Values 0.00 to
100.00%
Configuration
If you want to change the sensor input just change the CHANNEL register in the AI Block.
Block
Signal in
Device
OUT Value
Status
AI1
TM Flow %
0.00% - 100.00%
Good / Bad
Error Handling
If the IHP24 status is “Ok, FF-Fieldbus status on the AI channel goes to Good
If the IHP24 status is “Error”, FF-Fieldbus status on the AI channel goes to “Bad”