Valent Controls IOM 33 IOM-C1-0616
Part Number 474626
Description
UMT Name
= Editable
LCD Name
= Editable
Web UI Name
= Editable
Min
Max
Default
States
Supply Air Temperature
Maximum Cooling Setpoint
Supply Air Maximum Cooling
Setpoint
SUPPLY MAX COOL
Supply Max Cool Setpoint
70.0°F
95.0°F
95.0°F
—
Supply Air Temperature
Maximum Heating Setpoint
Supply Air Maximum Heating
Setpoint
SUPPLY MAX HEAT
Supply Max Heat Setpoint
70.0°F
95.0°F
95.0°F
—
Supply Air Temperature Minimum
Cooling Setpoint
Supply Air Minimum Cooling
Setpoint
SUPPLY MIN COOL
Supply Min Cool Setpoint
50.0°F
70.0°F
55.0°F
—
Supply Air Temperature Minimum
Heating Setpoint
Supply Air Minimum Heating
Setpoint
SUPPLY MIN HEAT
Supply Min Heat Setpoint
50.0°F
70.0°F
65.0°F
—
Supply Air Temperature Setpoint
Supply Air Temperature Setpoint
SUPPLY SETPT
Supply Temp Setpoint
50°F
95°F
70°F
—
Supply Fan Maximum Speed Spt
Supply Fan Max Speed Setpoint
SUP FAN MAX
Supply Fan Max Speed
50%
100%
100%
—
Supply Fan Minimum Speed
Setpoint
Supply Fan Min Speed
SUP FAN MIN
Supply Fan Min Speed
50%
100%
50%
—
Supply Fan Output
Supply Fan Output
SUPPLY FAN
Supply Fan
—
—
—
Off, On
Supply Fan Reaction Speed
(Duct Pressure)
Supply Fan Reaction Speed
SUPPLY REACTION
—
—
—
Medium
Very Slow, Slow, Medium,
Fast, Very Fast
Supply Fan Reaction Speed
(Space Pressure)
Supply Fan Reaction Speed
SUPPLY REACTION
—
—
—
Medium
Very Slow, Slow, Medium,
Fast, Very Fast
Supply Fan Speed
Supply Fan Speed
SUP FAN SPEED
Supply Fan Speed
0%
100%
—
—
Supply Fan Status
Supply Fan Status
SUP FAN STATUS
Supply Fan Status
—
—
—
Off, On
Supply Setpoint Calculated
Supply Setpoint Calculated
SUPPLY CALC
Calculated Supply Spt
—
—
—
—
Supply Temperature
Supply Temperature
SUPPLY TEMP
Supply Temperature
—
—
—
—
System Enable
System Enable
SYSTEM ENABLE
System Enable
—
—
Off
Off, On
Timed Override Duration
Timed Override Duration
—
TOV Duration
0 min
240 min
120 min
—
Unit Schedule
Unit Schedule
SCHEDULING
—
—
—
24/7
—
Unoccupied Outdoor Air Damper
Minimum
Unoccupied Outdoor Air Damper
Minimum
—
Unocc OA Damp Min
0%
100%
0%
—
Unoccupied Space Cooling
Setpoint
Unoccupied Space Cooling
Setpoint
UNOCC COOL
Unocc Cool Setpoint
75°F
85°F
80°F
—
Unoccupied Space Heating
Setpoint
Unoccupied Space Heating
Setpoint
UNOCC HEATING
Unocc Heat Setpoint
55°F
70°F
60°F
—
Unoccupied Space Relative
Humidity Setpoint
Unoccupied Space Humidity
Setpoint
—
Space Unocc RH Spt
0%
100%
68%
—
Unoccupied Supply Fan Offset
Unoccupied Supply Fan Speed
Offset
—
—
0%
50%
0%
—
Water Source Heat Pump Cold
Start Duration
WSHP Cold Start Duration
—
WSHP Cold Start
0 sec
300 sec
60 sec
—
Water Source Heat Pump Cold
Start Enable Temperature
WSHP Cold Start Enable Temp
—
WSHP Cold Start
0°F
60°F
30°F
—
Water Source Heat Pump
Compressor Off Water Valve
Position
WSHP Compressor Off Water
Valve Position
COMP OFFVLVPOS
WSHP Valve Off
0%
100%
100%
—
Water Source Heat Pump
Condenser Temperature Setpoint
WSHP Condenser Temperature
Setpoint
—
WSHP Cond Temp
90°F
120°F
115°F
—
Water Source Heat Pump
Suction Temp Low Limit
WSHP Suction Temp Low Limit
Safety
WSHP SUC LOWLIM
WSHP Suction Safety
0°F
40°F
25°F
—
Water Source Heat Pump Water
Valve Max Closed Position Setpt
WSHP Valve Max Closed
Position
—
—
50%
100%
85%
—
Winter Ramp Control Type
Winter Ramp Control Type
—
Winter Control
—
—
Supply
Fan
Supply Fan, Damper
Winter Ramp OA Enable Setpoint
Cold OAT Setpoint
—
—
20°F
60°F
40°F
—
Winter Ramp Type In Control
Winter Ramp Type In Control
—
—
—
—
—
—