Valent Controls IOM 32 IOM-C1-0616
Part Number 474626
Description
UMT Name
= Editable
LCD Name
= Editable
Web UI Name
= Editable
Min
Max
Default
States
Optimal Start/Stop Earliest Stop
Time
Earliest Stop Time
Earliest Stop Time
0 hr
24 hr
18 hr
Optimal Stop Enable
Enable Optimal Stop
Enable Optimal Stop
No
No, Yes
Outdoor Air Damper Maximum
Position
Outdoor Air Damper Maximum
OAD MAX POS
OA Damper Max
0%
100%
100%
Outdoor Air Damper Minimum
Position
Outdoor Air Damper Minimum
OAD MIN POS
OA Damper Min
0%
100%
30%
Outdoor Air Dewpoint Deadband
Outdoor Dewpoint Deadband
0°F
15°F
3°F
Outdoor Air Enthalpy
Outdoor Enthalpy
OUTDOOR ENTH
OA Enthalpy
0 Btu/lb
60 Btu/lb
Outdoor Air Relative Humidity
Outdoor Air Relative Humidity
OUTDOOR RH
Outdoor Air RH
0%
100%
Outdoor Air Temperature
Outdoor Air Temperature
OA TEMP
Outdoor Air Temp
-13°F
326°F
Outdoor Dewpoint
Outdoor Dewpoint
OA Dewpoint
Outdoor Dewpoint Setpoint
Outdoor Dewpoint Setpoint
OA DEWPOINT SPT
OA Dewpoint
55°F
100°F
99°F
Overcool Offset
Overcool Offset
2.0°F
10.0°F
4.0°F
Preheat Ambient Setpoint
Preheat Ambient Setpoint
Preheat Setpoint
-50.0°F
65.0°F
10.0°F
Preheat Output
Preheat Output
PREHEAT
Pre Heater
Off, On
Refrigerant Pressure Circuit A
Refrigerant Pressure Circuit A
PRESSURE CIRC A
Refrigerant A
0 psi
750 psi
Refrigerant Pressure Circuit B
Refrigerant Pressure Circuit B
PRESSURE CIRC B
Refrigerant B
0 psi
750 psi
Space Dewpoint
Space Dewpoint
Space Dewpoint
Space Dewpoint
Dehumidification Disable
Setpoint
Space Dewpoint
Dehumidification Cutout
Space DPT Disable
0.0°F
70.0°F
45.0°F
Space Enthalpy
Space Enthalpy
SPACE ENTH
Space Enthalpy
0 Btu/lb
60 Btu/lb
Space Pressure High Limit
Setpoint
Space Pressure High Limit
Setpoint
HIGH LIMIT
Space Pressure High Lim
0.000
InWc
+0.500
InWc
+0.200
InWc
Space Relative Humidity
Space Relative Humidity
SPACE RH
Space RH
0%
100%
Space Relative Humidity
Occupied Deadband Setpoint
Occupied Space Humidity Low
Deadband
0%
15%
5%
Space Relative Humidity Setpoint
Space Relative Humidity Setpoint
SPACE RH SPT
Space RH Setpoint
0%
100%
55%
Space Relative Humidity
Unoccupied Deadband Setpoint
Unoccupied Space Humidity
Low Deadband
0%
15%
5%
Space Reset Deadband
Space Reset Deadband
0°F
2°F
0.25°F
Space Static Pressure
Space Pressure
PRESSURE
Space Pressure
-0.5 InWc
+0.5 InWc
Space Static Pressure Setpoint
Setpoint
SETPOINT
Space Pressure Setpoint
-0.500
InWc
+0.500
InWc
+0.050
InWc
Space Temperature
Space Temperature
SPACE TEMP
Space Temperature
-13°F
326°F
Space Temperature Adjust
Disable
Local Temp Adjust Disable
LOCAL ADJ DISABLE
False
False, True
Space Temperature Cooling
Setpoint
Space Cooling Setpoint
Space Temperature Heating
Setpoint
Space Heating Setpoint
Space Temperature Setpoint
Space Temperature Setpoint
SPACE SETPT
Space Temp Setpoint
60°F
90°F
74°F
Space Temperature Setpoint
Offset
Space Temperature
Setpoint Offset
SPACE OFFSET
Space Temp Offset
0.0°F
20.0°F
0.0°F
Space Setpoint Slider
Space Setpoint Slider
SPT SLIDER
Space Setpoint Slider
Supply Air Cooling High
Deadband Setpoint
Supply Air Cooling High
Deadband
Supply Deadband
0.0°F
8.0°F
0.0°F
Supply Air Cooling Low
Deadband Setpoint
Supply Air Cooling Low
Deadband
Supply Deadband
0.0°F
8.0°F
0.0°F
Supply Air Deadband Enable
Setpoint
Temperature Control PID
Deadband Enable
Deadband Enable
Disable
Enabled, Disabled
Supply Air Heating High
Deadband Setpoint
Supply Air Heating High
Deadband
Supply Deadband
0.0°F
8.0°F
0.0°F
Supply Air Heating Low
Deadband Setpoint
Supply Air Heating Low
Deadband
Supply Deadband
0.0°F
8.0°F
0.0°F
Supply Air Temperature Control
Supply Air Temperature Control
SUPPLY CONTROL
Auto
Auto, Yes
Supply Air Temperature High
Limit
Supply Temperature High Limit
Supply High Limit
90°F
120°F
120°F
Supply Air Temperature High
Limit Alarm Delay
Supply High Temp Alarm Delay
3 min
15 min
3 min
Supply Air Temperature Low
Limit
Supply Temperature Low Limit
Supply Low Limit
30°F
50°F
35°F