Valent VX Series Controller20
TemperaTure seT poinT
This screen only appears if supply temp control, space reset, or return reset is
selected as the reset control mode.
Set Point Selections:
Local – The space set point will be constant; set from screen (e.g. 72°F).
BMS – The BMS can directly control the space temperature set point (requires
BMS communication option).
T-Stat – The space set point will be adjustable from the space thermostat.
Reference Appendix: Room Thermostat Quick Start for additional information.
heaT cool deadband
This screen only appears if space reset or return air reset is selected as the reset
control mode. The heat cool deadband allows for separate cooling and heating
set points when the reset control mode is set for space reset or return air reset.
supply seT poinTs
Cooling and heating supply set points screens only appear if outdoor reset, space
reset, or return air reset is selected. These screens allow the user to set the min
and max set point limits for cooling or heating operation. The controller will adjust
the supply temperature set point between the set limits depending on mode of
operation.
mode swiTch display
This screen displays the delay time required before switching between heating
and cooling mode.
sTarTup display
This screen displays the delay time after the fans have started and tempering
begins
Menu
ouTside seT poinTs
This screen only appears if outside reset is selected as the reset control mode.