Valent VX Series Controller 43
VARIABLE DESCRIPTION
ACTIVE
TEXT
INACTIVE
TEXT
BACNET MODBUS
OBJECT
INSTANCE
OBJECT
TYPE
ACCESS HYST INDEX
REGISTER
TYPE
SIZE
Analog Inputs - Read Only
Circuit_A_Discharge_
Temp_Analog_Input
Circuit A Discharge
Temperature
1 AI
ReadCOV_
NoWrite
0.1 30195 Input 2
Circuit_A_Suction_
Temp_Analog_Input
Circuit A Suction
Temperature
3 AI
ReadCOV_
NoWrite
0.1 30199 Input 2
Cold_Coil_1_Temp_
Analog_Input
Cold Coil 1 Temperature 25 AI
ReadCOV_
NoWrite
0.1 30243 Input 2
CL_Coil_Spt_Temp
Controls Lite Cooling Coil
Set Point Temperature
value
31 AI
ReadCOV_
NoWrite
0.1 30255 Input 2
CL_Supply_Spt_Temp
Controls Lite Supply Set
Point Temperature value
32 AI
ReadCOV_
NoWrite
0.1 30257 Input 2
Outside_Air_Temp_
Analog_Input
Outside Air Temperature 37 AI
ReadCOV_
NoWrite
0.1 30267 Input 2
Space_Temp_Analog_
Input
Space Temperature 44 AI
ReadCOV_
NoWrite
0.1 30281 Input 2
Supply_Temp_Analog_
Input
Supply Temperature 45 AI
ReadCOV_
NoWrite
0.1 30283 Input 2
Outside_RH_Analog_
Input
Outside % Relative
Humidity
86 AI
ReadCOV_
NoWrite
0.1 30349 Input 2
Space_RH_Analog_
Input
Space % Relative Humidity 89 AI
ReadCOV_
NoWrite
0.1 30355 Input 2
Space_Static_
Pressure_Analog_Input
Space Static Pressure 94 AI
ReadCOV_
NoWrite
0.01 30365 Input 2
Supply_Duct_Static_
Pressure_Analog_Input
Supply Duct Static Pressure 95 AI
ReadCOV_
NoWrite
0.01 30367 Input 2
Space_CO2_1_
Analog_Input
Space 1 CO2 ppm 116 AI
ReadCOV_
NoWrite
10 30401 Input 2
Circuit_A_Discharge_
Pressure_Analog_Input
Circuit A Discharge
Pressure
119 AI
ReadCOV_
NoWrite
0.1 30407 Input 2
Circuit_A_Suction_
Pressure_Analog_Input
Circuit A Suction Pressure 120 AI
ReadCOV_
NoWrite
0.1 30409 Input 2
Circuit_B_Discharge_
Pressure_Analog_Input
Circuit B Discharge
Pressure
121 AI
ReadCOV_
NoWrite
1 30411 Input 2
Aux_In_Customer_1
Customer defined auxiliary
input
640 AI
ReadCOV_
NoWrite
0.1 30639 Input 2
Aux_In_Customer_2
Customer defined auxiliary
input
642 AI
ReadCOV_
NoWrite
0.1 30641 Input 2
Aux_In_Customer_3
Customer defined auxiliary
input
644 AI
ReadCOV_
NoWrite
0.1 30643 Input 2
Aux_In_Customer_4
Customer defined auxiliary
input
646 AI
ReadCOV_
NoWrite
0.1 30645 Input 2
Aux_In_Customer_5
Customer defined auxiliary
input
648 AI
ReadCOV_
NoWrite
0.1 30647 Input 2
Aux_In_Customer_6
Customer defined auxiliary
input
650 AI
ReadCOV_
NoWrite
0.1 30649 Input 2
Appendix E: Points List