Valent VX Series Controller44
VARIABLE DESCRIPTION
ACTIVE
TEXT
INACTIVE
TEXT
BACNET MODBUS
OBJECT
INSTANCE
OBJECT
TYPE
ACCESS HYST INDEX
REGISTER
TYPE
SIZE
Analog Values - Read/Write - Commandable
Temperature_Set Point
Main Temperature Set
point. Supply, Space, or
Return target temperature
1 AV
ReadCOV_
Commandable
0 40001 Holding 2
Temperature_Heat_
Cool_Deadband
Heat/Cool Spt Deadband
when Room or Return
control is active. Clg Spt =
Deadband /2 + Temp Spt.
Htg Spt = Deadband /2 -
Temp Spt.
2 AV
ReadCOV_
Commandable
0 40003 Holding 2
Cooling_Coil_Set
Point_Min
Cooling Coil Leaving Air
Set Point
3 AV
ReadCOV_
Commandable
0 40005 Holding 2
Dehumidification_Set
Point
Dehumidification Set Point.
%RH for Space or Return
control.
5 AV
ReadCOV_
Commandable
0 40009 Holding 2
Outside_Dewpoint_Set
Point
Outside Dewpoint
Dehumidification Trigger
Set Point
6 AV
ReadCOV_
Commandable
0 40011 Holding 2
Indoor_Dewpoint_Set
Point
Indoor Dewpoint
Dehumidification Trigger
Set Point
7 AV
ReadCOV_
Commandable
0 40013 Holding 2
Unocc_Indoor_
Dewpoint_Set Point
Unoccupied Indoor
Dewpoint Dehumidification
Trigger Set Point
9 AV
ReadCOV_
Commandable
0 40017 Holding 2
Unoccupied_Cooling_
Set Point
Unoccupied Cooling Set
Point
10 AV
ReadCOV_
Commandable
0 40019 Holding 2
Unoccupied_
Dehumidification_Set
Point
Unoccupied
Dehumidification %RH Set
Point
11 AV
ReadCOV_
Commandable
0 40021 Holding 2
Unoccupied_Heating_
Set Point
Unoccupied Heating Set
Point
12 AV
ReadCOV_
Commandable
0 40023 Holding 2
Economizer_Temp_
Enable_Set Point
Economizer Ambient Temp
Enable Set Point. Allow
Econ when OAT<Spt
16 AV
ReadCOV_
Commandable
0 40031 Holding 2
Economizer_Enthalpy_
Enable_Set Point
Economizer Enthalpy
Enable Set Point.
Allow Econ when OA
Enthalpy<Spt
17 AV
ReadCOV_
Commandable
0 40033 Holding 2
Outside_RH_from_
BMS
Outside RH from BMS. Used
when source selection is
set to BMS.
21 AV
ReadCOV_
Commandable
0.1 40041 Holding 2
Outside_Temp_from_
BMS
Outside Temp from BMS.
Used when source selection
is set to BMS.
22 AV
ReadCOV_
Commandable
0.1 40043 Holding 2
Return_RH_from_BMS
Return RH from BMS. Used
when source selection is
set to BMS.
23 AV
ReadCOV_
Commandable
0.1 40045 Holding 2
Return_Temp_from_
BMS
Return Temp from BMS.
Used when source selection
is set to BMS.
24 AV
ReadCOV_
Commandable
0.1 40047 Holding 2
Space_1_CO2_from_
BMS
Space 1 CO2 from BMS.
Used when source selection
is set to BMS.
25 AV
ReadCOV_
Commandable
0.1 40049 Holding 2
Space_RH_from_BMS
Space RH from BMS. Used
when source selection is
set to BMS.
28 AV
ReadCOV_
Commandable
0.1 40055 Holding 2
Space_Static_from_
BMS
Space Static from BMS.
Used when source selection
is set to BMS.
29 AV
ReadCOV_
Commandable
0.1 40057 Holding 2
Space_Temp_from_
BMS
Space Temp from BMS.
Used when source selection
is set to BMS.
30 AV
ReadCOV_
Commandable
0.1 40059 Holding 2
Cooling_Lockout_Set
Point
Cooling Ambient Lockout
Set Point
31 AV
ReadCOV_
Commandable
0.1 40061 Holding 2
Heating_Lockout_Set
Point
Heating Ambient Lockout
Set Point
32 AV
ReadCOV_
Commandable
0.1 40063 Holding 2
Space_Static_
Pressure_Set Point
Space Static Pressure Set
Point
37 AV
ReadCOV_
Commandable
0.1 40073 Holding 2
Appendix E: Points List

Other manuals for valent VX Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the valent VX Series and is the answer not in the manual?

valent VX Series Specifications

General IconGeneral
Brandvalent
ModelVX Series
CategoryAir Handlers
LanguageEnglish

Related product manuals