Charging the refrigerant cycle REVO E Evacuation and Charging Instructions
18
4.3. Final inspection
On successfully charging the unit the following checks must be carried
out:
Check for leak-proof condition
Cut-off valves opened
Refrigerant must be free from bubbles in the sight glass.
Ensure a sufficient amount of charged refrigerant by a measurement
of subcooling: Delta K approx. 10K ±2K
After 10 minutes of test running the compressor check the oil level in
the compressor: Set value: middle of sight glass.
Check the shut-off pressure levels of the high-low pressure switches
by e.g. covering of the condenser / disconnecting the plug of the
magnetic valve!
NOTE:
Check position of the solenoid valve connector cable outlet -
>
the cable outlet must point down.
Reason: to avoid water ingress into the connector housing
(see homepage "Technical Update / Solenoid valve")
Check the functioning of ambient / fresh air flaps.
Check whether the water valves are closed at maximum cooling up
to 100%.