Output configuration
Parameter Description Range Default
CP 12 Manual Override Mode:
Allows manual control of the floating outputs for using the
controller as positioner or during commissioning.
ON, OFF OFF
CP 13 Running time FO1 (TCY-FT4-U = heating output)
The total time it takes for the actuator to run from fully open
to fully closed or from fully closed to fully open
0-255s 90s
CP 14 Minimum running time FO1 (TCY-FT4-U = heating output)
The minimum time the output runs once it starts. This setting
prevents frequent switches with very short running times.
0-255s 3s
CP 15 Running time FO2 (TCY-FT4-U = cooling output)
The total time it takes for the actuator to run from fully open
to fully closed or from fully closed to fully open
0-255s 90s
CP 16 Minimum running time FO2 (TCY-FT4-U = cooling output)
The minimum time the output runs once it starts. This setting
prevents frequent switches with very short running times.
0-255s 3s
CP 17
Maximum Output in Economy (unoccupied) Mode
Reduces the load on the system when is the space is
unoccupied.
0 – 100 % 50%