TCY-FT-U
Configuration
 
Doc: 70-00-0128B, V1.2, 20110621  © Vector Controls GmbH, Switzerland  Page 8 
Subject to alteration 
Input configuration 
Parameter Description  Range  Default 
CP 18  Configuration of remote input (X1) 
0 = Control Input  
1 = Comfort/Economy Mode switch 
2 = Comfort/OFF Mode switch  
3 = Keycard switch function   
4 = Output enable  
0…4 0 
CP 19  Activation delay (minutes): 
The time the binary input needs to be open before Economy or 
OFF mode is activated. 
0…255 min  5 
CP 20  Fixed setpoint for key card function in heating mode  0–60°C (32..160°F)  17°C (63°F) 
CP 21  Fixed setpoint for key card function in cooling mode  0–60°C (32..160°F)  27°C (81°F) 
CP 22  For TCY-FT2-U only: Enable Auto changeover  ON, OFF  OFF 
CP 23  For TCY-FT2-U only: Auto changeover limit heating  0–60°C (32..160°F)  30°C (86°F) 
CP 24  For TCY-FT2-U only: Auto changeover limit cooling  0–60°C (32..160°F)  15°C (59°F) 
Î  Configuring the function of the external input X1 
The external input X1 may be configured for several functions: 
 
CP18 = 0  External control input  The control input is provided by the external input. The internal input 
will not be used.  
CP18 = 1  Switching Economy and 
Comfort modes 
Economy (unoccupied) and Comfort (occupied) modes are controlled 
through an external contact by connecting X1 through a dry contact to 
signal common. This function may be used together with key card 
switches for hotels or motion detectors for offices. 
CP18 = 2  Switching Energy Hold 
OFF and Comfort 
modes 
Opening the external temperature input will force the unit into the OFF 
operation mode. The operation mode cannot be overridden by using the 
terminal. Connecting the binary input to GND returns control of the 
operation mode to the terminal. This function may be used as window 
contact to prevent loss of energy.  
CP18 = 3  Key card function  As with CP18 = 1, the key card function switches economy 
(unoccupied) and comfort (occupied) modes. Instead of using the 
setpoint shift, the setpoints in unoccupied mode are defined by 
parameter CP20 and CP21.  
CP18 = 4  Output enable / Dew 
point sensor 
This may be used for a dew point sensor input. Output will switch off if 
contact opens. 
Î  Configuring auto changeover input X2 (TCY-FT2-U only): 
The auto changeover function automatically changes heating and cooling mode based on supply media 
temperature or outdoor temperature. The difference between the two is in the values of the changeover limits 
CP23 and CP24. See table below for recommended settings. 
Heating and cooling may be as well changed by an open contact switched to signal ground. Note: all signal 
ground levels of involved controllers must be the same in case more than one controller is switched.  
Î  Recommended settings for CP23 and CP24: 
Change over mode  Relation CP23 to CP24  Example CP23  Example: CP24 
Supply media  CP23 > CP24  25°C (77F)  18°C (64F) 
Outside temperature  CP23 < CP24  15°C (59F)  25°C (77F) 
Dry contact: Heating if contact closed  CP23 > CP24  25°C (77F)  15°C (59F) 
Dry contact: Cooling if contact closed  CP23 < CP24  15°C (59F)  25°C (77F)