5 Configuration (parameter options)
Content of chapter
5.1 Parameter usage _________________________________________________________________________ 13
5.1.1 Parameter number, resolution and data format ______________________________________________ 13
5.1.2 Modbus access (TRA-F221-A only) ________________________________________________________ 14
5.2 Setting controller parameter with user interface_________________________________________________ 14
5.3 Modbus settings (TRA-F221-A only) __________________________________________________________ 14
5.3.1 Parameter P00x overview _______________________________________________________________ 14
5.4 Operating options ________________________________________________________________________ 15
5.4.1 Parameter P1xx overview _______________________________________________________________ 15
5.5 Quick system and output configuration (application specific) _______________________________________ 16
5.5.1 Parameter P000 overview _______________________________________________________________ 16
5.5.2 Application modes: Wiring diagrams of outputs ______________________________________________ 16
5.6 System and output configuration ____________________________________________________________ 17
5.6.1 Parameter P2xx overview _______________________________________________________________ 17
5.6.2 Application modes: Valve control diagrams _________________________________________________ 18
5.6.3 Application modes: Wiring diagrams of outputs ______________________________________________ 19
5.6.4 Manual vs. auto heat/cool change ________________________________________________________ 20
5.6.5 3-position valve control ________________________________________________________________ 21
5.6.6 Modulating valve control ________________________________________________________________ 21
5.6.7 Fan extension time for electric heater _____________________________________________________ 21
5.6.8 Periodic fan kick ______________________________________________________________________ 21
5.6.9 Floor heating system with or without floor temperature limitation ________________________________ 21
5.7 Set points ______________________________________________________________________________ 22
5.7.1 Parameter 3xx overview ________________________________________________________________ 22
5.7.2 Temperature set point types ____________________________________________________________ 22
5.8 Control settings _________________________________________________________________________ 24
5.8.1 Parameter 4xx overview ________________________________________________________________ 24
5.8.2 Proportional control (proportional band or switching differential) _________________________________ 24
5.8.3 Integral control (integral time) ___________________________________________________________ 24
5.8.4 On/Off control ________________________________________________________________________ 25
5.8.5 3-position control _____________________________________________________________________ 25
5.8.6 Modulating control ____________________________________________________________________ 25
5.8.7 Graphics for modulating and 3-position control ______________________________________________ 25
5.8.8 On/Off control for 4-pipe application heating and cooling mode __________________________________ 26
5.8.9 Modulating control for 4-pipe application heating and cooling mode ______________________________ 26
5.8.10 Analog fan control in automatic mode (on/off control) _________________________________________ 27
5.8.11 Analog fan control for modulating and 3-position valve ________________________________________ 27
5.8.12 3-stage fan control in automatic mode (Modulating valve) ______________________________________ 27
5.9 Temperature and digital inputs ______________________________________________________________ 28
5.9.1 Parameter P5xx overview _______________________________________________________________ 28
5.9.2 P500/502: 2 = Heat/cool changeover or floor temperature sensor (NTC or DI) ______________________ 28
5.9.3 P500/502: 3/4 = Occupation sensor_______________________________________________________ 29
5.9.4 P500: 5 = Door switch (DI) and P502: 3 or 4 = Occupation sensor (DI) ___________________________ 29
5.9.5 P500/502: 7 = Dew point sensor _________________________________________________________ 29
5.9.6 P500/502 digital input assignment ________________________________________________________ 29
5.10 Load and store default settings ______________________________________________________________ 30
5.10.1 With user interface ____________________________________________________________________ 30
5.10.2 With Modbus _________________________________________________________________________ 30
5.1 Parameter usage
5.1.1 Parameter number, resolution and data format
Parameter number and Modbus data address are the same. They are listed in column “Par/Addr” as decimal number.
E.g. P001 is parameter 001 and has Modbus data address 1.
All temperature related parameters are given in °C for Modbus. Only in the user interface values can be shown in °F.
Parameters without multiplier have a resolution of 1. Parameters with multiplier 10 have a resolution of 0.1.
For example, the default value of the Comfort temperature set point (P300) is 20.0°C and the value read via Modbus is
200 (because multiplier 10 is used for P300).
The multiplier is only used for Modbus data access. On the user interface, the values are displayed in normal resolution.
Parameter with values below 0 (zero) are given as signed integer values.