This alarm occurs when the pump-On and pump-Off pressures
are reading the same value and are within the range of 5 to 15
psi.
Probable causes:
1. STP did not switch On.
2. Low STP pump pressure.
3. Bad transducer.
4. Bad PLLD Interface Module.
SHORT ALARM - PLLD ONLY (Pre 19 Only)