EasyManua.ls Logo

Veeder-Root PLLD - Setup Data Warning

Veeder-Root PLLD
20 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
14
This alarm occurs when an error has been made in program-
ming. In Version 17 and later, this will also occur if the line length
has not been programmed. The line length default is 501 feet
and will cause a SETUP DATA WARNING if the Service Contrac-
tor does not enter the line length.
NOTE: The default line type is set to FLEX A (white Envirof-
lex PP1501). If the actual line type is not FLEX A, and the
Service Contractor does not select the correct line type, the
result may be a GROSS LINE FAIL.
SETUP DATA WARNING