Periodic or Annual Test Warning (Pre 19) / Periodic or Annual Test Needed Warning (19 & Higher)
The system failed to complete or pass a Periodic (0.20 gph) or
Annual (0.10 gph) test in the programmed number of days.
Probable Causes:
1. There are Periodic or Annual test failures [Check test history
to determine if tests are failing; if they are, follow procedures
in Periodic or Annual Test Fail alarms (Page 3)].
2. Pump-on pressure readings <22 psi.
3. (Ver 17 & 18 only)
Active High Pressure Warning or Alarm: follow procedures
on Page 4 to correct the High Pressure condition.
(Ver 19 and higher)
The line is not venting when the pump is shut Off. There
should be at least a 2 psi difference between P
on
and P
off
.
Print out the 0.2 or 0.1 diagnostic. The No Vent test aborts
message X out of 10 tests, indicates how many tests have
been aborted due to a non-venting problem. Check for
stuck relay, Functional Element not diabled (Red Jacket),
incorrect Check Valve (FE Petro), or incorrectly adjusted
Check Valve (FE Petro).
4. Active Continuous Pump Warning/Alarm or Continuous
Handle Alarm.
5. If the site is extremely busy, especially if blenders are
present, there may not be sufficient idle time to complete a
Periodic or Annual test unless the station is shut down.